KBH Energy s.r.o.
|
Tel.: | +420 461 105 060 |
| Na Spravedlnosti 1533 | +420 461 100 112 | |
| Pardubice 530 02 | Mobil: | +420 777 730 001 |
| IČ: 275 02 279 | +420 777 730 004 | |
| DIČ: CZ275 02 279 | +420 777 730 002 | |
| Technické oddělení: | Tel.: | +420 461 105 060 |
| E-mail: kbh@kbh.cz | Fax: | +420 463 119 852 |
n High capabilityn For output up to 75 kvar n Copper winding n Thermal switch
Filter reactors VINDEX match modern standards a are designed for usage in power factor correction and improvement installations, first of all like protection of capacitors in networks with appearance of harmonic frequencies.
Safety of filter reactor in use is guaranteed by its construction, e.g. dimension of inner wires , insulation strength and integrated temperature sensors with NC contact adjustable for range 110 to 140 °C (upon request).
Filter reactors VINDEX are suitable to low voltage networks for protection of capacitors against harmonic influence, preventing any amplification of harmonics caused by resonance and and dumping of inrush currents caused by switching.
There are just most frequently produced and used types of capacitors mentioned in Table “Production range”
| Rated voltage 400 V, 50 Hz, capacitor voltage 440 V, detuning factor 7 % |
| Typ | QC (kvar) | CN (µF) | QCL (kvar) | LN (mH) | Current IN (A) | Current ILIN (A) |
| VINDEX 5/440-7-4/400 | 5 | 3 × 28 | 4,4 | 8,63 | 6,4 | 8,3 |
| VINDEX 7,5/400-7-7/400 | 7,5 | 3 × 40 | 6,7 | 5,75 | 9,6 | 12,5 |
| VINDEX 10/440-7-9/400 | 10 | 3 × 57 | 8,9 | 4,31 | 12,8 | 16,7 |
| VINDEX 12,5/440-7-11/400 | 12,5 | 3 × 68 | 11,1 | 3,45 | 16 | 20,8 |
| VINDEX 14/440-7-12,4/400 | 14 | 3 × 77 | 12,4 | 3,17 | 17,5 | 22,8 |
| VINDEX 15/440-7-13/400 | 15 | 3 × 82 | 13,3 | 2,88 | 19,2 | 25 |
| VINDEX 20/440-7-18/400 | 20 | 3 × 111 | 17,9 | 2,15 | 25,6 | 33,3 |
| VINDEX 25/440-7-22/400 | 25 | 3 × 137 | 22,2 | 1,73 | 31,9 | 41,7 |
| VINDEX 28,1/440-7-25/400 | 28,1 | 3 × 154 | 25 | 1,53 | 32,9 | 42,2 |
| VINDEX 30/440-7-26/400 | 30 | 3 × 166 | 26 | 1,46 | 37,8 | 50 |
| VINDEX 40/440-7-36/400 | 40 | 3 × 219 | 36 | 1,07 | 51,3 | 66,7 |
| VINDEX 50/440-7-44/400 | 50 | 3 × 274 | 44 | 0,86 | 63,9 | 83,4 |
| VINDEX 56,2/440-7-50/400 | 56,2 | 3 × 306 | 50 | 0,77 | 64,9 | 84,4 |
| Rated voltage 400 V, 50 Hz, capacitor voltage 525 V, detuning factor 7 % |
| Typ | QC (kvar) | CN (µF) | QCL (kvar) | LN (mH) | Current IN (A) | Current ILIN (A) |
| VINDEX 20/525-7-12,5/400 | 20 | 3 × 28 | 12,5 | 8,63 | 6,4 | 8,3 |
| VINDEX 40/525-7-25/400 | 40 | 3 × 40 | 25 | 5,75 | 9,6 | 12,5 |
| VINDEX 80/525-7-50/400 | 80 | 3 × 57 | 50 | 4,31 | 12,8 | 16,7 |
| Rated voltage 400 V, 50 Hz, capacitor voltage 525 V, detuning factor 14 % |
| Typ | QC (kvar) | CN (µF) | QCL (kvar) | LN (mH) | Current IN (A) | Current ILIN (A) |
| VINDEX 18,8/525-14-12,5/400 | 18,8 | 3 × 68 | 12,5 | 9,35 | 17,4 | 23,3 |
| VINDEX 37,5/525-14-25,3/400 | 37,5 | 3 × 137 | 25,3 | 3,48 | 37,6 | 48,3 |
| VINDEX 75/525-14-50,6/400 | 75 | 3 × 280 | 50,6 | 1,36 | 72,8 | 96,7 |
Filter reactors VINDEX are of capable construction, with iron core double air gap and copper coil winding impregnated with polyester resin (class F).
Standard product range is designed for resonance frequency 189 Hz (p=7%, 4th dominant harmonic) and capacitors with rated voltage 440 V or for 134 Hz (p=14 %) and 525 V capacitors. The dissipation losses rank between 4 and 6 W/kvar of installed reactive power. We guarantee tolerance of inductance max ±3% from rated inductance as mentioned on type plate of each reactor.
There is an integrated thermal NC switch inside central coil, which can be set to be opened within temperatures from 110 to 140 °C (this feature allows external monitoring or disconnection of the reactor.
Up to 30 kvar reactors are provided with terminal blocks, from 30 kvar with copper connecting flags 20x5 mm for M8 screws.
Standard reactors VINDEX can be operated:
Maximum current linearity, when inductance doe not decrease by more then 5 % is 1,6 to 2,5 multiple of rated reactor current.
Exceeding of required parameters will lead to overheating and thermal destruction of reactor.
Filter reactors VINDEX shall be installed in rooms with ambient temperature from -5 to 40 °C.
Permissible daily average temperature must not exceed 35 °C.
Under these conditions the temperature of reactor does not exceed 110 °C. Materials used for reactor production insulation strength min. to 135 °C (class B).
Reactors VINDEX are designed for indoor mounting, degree of protection IP00, permissible humidity max 95 % without dew, natural or forced cooling.
|
Allowed harmonic load for continuous operation |
| IN | 10 % | U7 | 5 % |
| U3 | 0,5 % | U11 | 3,5 % |
| U5 | 6 % | U13 | 3 % |